One Analog and 5 KYZ Circuits
Source: Da-Tel Research Co., Inc.
System 1 is designed to telemeter power measurements: volts, amps, kWh, kVARs
Purpose:
System 1 is designed to telemeter power measurements: volts, amps, kWh, kVARs. The system provides 1 analog point and 5 KYZ relay links using mercury-wetted relay contacts. Larger systems can be provided as specified. Readings are taken by using dedicated telephone lines between stations or a station dial-up on the public dial network. A standard telephone at the local receiving site dials the remote and initiates the readings. The dial-up interface will be available in 2000.
Specifications
- Center Frequency: 1860Hz
- Bit Rate: 480BPS
- Update Time (Response) .037 seconds
- Maximum Rate over KYZ Contact Links for 10% Pulse Shortening: 2.5PPS (150PPM)
- Analog Accuracy: 0.5%
- Frequency Stability: .15% ±2HZ from -10°C to +55°C.
- Analog Update Time: .037 seconds
- Analog Input: 0-1.0V
- Analog Output: 0-1.0V
- Tone Levels: -30 to -9dBm, -10dBm fixed transmit level.
- FCC Registered
- Power: 115Vac, 50/60Hz or 125Vdc, 15W
Da-Tel Research Co., Inc., 932 N. Park Ave., P.O. Box 1206, Montrose, CO 81402. Tel: 970-249-6129; Fax: 970-249-8919.